Register

63A Modular changeover switch

The unique solution for the control between two power supplies. Has been developed in order to extend the current range of modular changeover switch to 63A. Meets our customers’ need to have a changeover switch compatible with the hager modular enclosure (fitted on DIN rail clip and for normal safety application).

Technical information

  • 63A modular changeover switch can be fitted into any standard DIN-rail mounted enclosure.
  • Its design is compatible with all other hager modular devices, such as MCBs and RCCBs.
  • Switch comes in 2P and 4P version, for single and three phase applications.
  • The incoming side must be protected against short circuit and for isolation with an appropriate MCB 63A min. 4.5KA curve C.
  • The 63A changeover switch comes with a centre-off position.

Electrical characteristic

RefSF263SF463
Nb of pole
2
4
Operational voltage (Ue)
230V
400V
Thermal current Ith (40C)
63A
63A
Operational frequency
50/60hz
50/60hz
Rated insulation voltage (Ui)
500V
500V
Rated impulse withstand voltage Uimp
4kV
4kV
Working temperature
-20C +50C
-20C +50C
Storage temperature
-40C +80C
-40C +80C